Pick conduit fill or voltage drop mode, enter the circuit the sizer flags NEC violations live.
Trade size
Conductors THHN/THWN-2 copper
Raceway package for the estimate
NEC fill meter
7.5%
Raceway fill
7.5%
FILL
Bill of materials+0% waste
EMT 3/4" raceway
Within 40% NEC limit (Ch.9 Table 1)
Net 3 conductors · Waste —
Recommended conduit
Smallest EMT that clears the limit
Net — · Waste —
Conductor package
THHN/THWN-2 copper
Net 3 × 100 ft · Waste —
Cost projection
Saved on this device · No account · No cloud
Sizing aid only verify against the adopted NEC edition and your AHJ.
Total · $311.00
7.5% fill
NEC Chapter 9 Table 1: 53% fill for 1 wire, 31% for 2 wires, 40% for 3+ wires. Overfill is a code violation.
Pick conduit fill or voltage drop mode, enter the circuit the sizer flags NEC violations live.
Voltage drop = 2 × K × I × L ÷ circular mils (√3 factor for 3-phase). NEC recommends ≤ 3% on branch circuits.
Recommendations pick the smallest stock conduit / wire gauge that clears the limit.
Ft = run × conductors × 1.1
Single-phase: Vd = 2 × K × I × L ÷ circular mils, where K is 12.9 for copper and 21.2 for aluminum; use √3 instead of 2 for three-phase. The tool runs this against your run length, load, and wire gauge, then flags drops over the NEC's recommended 3% for branch circuits.
NEC Chapter 9 Table 1 limits fill to 53% for one wire, 31% for two wires, and 40% for three or more wires — overfill is a code violation. Enter your conductors and the tool checks your raceway against these limits live.
It depends on the wire sizes and the conduit's inside diameter — the tool applies NEC Chapter 9 fill percentages to your exact conductor mix and tells you whether the raceway clears or violates. Verify against the NEC edition your AHJ enforces before pulling wire.
Pick voltage-drop mode, enter run length and load amps, and the sizer recommends the smallest stock wire gauge that holds drop at or under 3% on the branch circuit. NEC recommends ≤ 3% on branch circuits (5% total feeder plus branch) as a design fine-print note.
The NEC recommends a maximum 3% drop on branch circuits and 5% combined for feeder plus branch, as a fine-print design note rather than a hard rule. The tool flags anything over 3% on branch runs so you can upsize the wire or shorten the run.